CONTROL
CIRCUITS
A. INTRODUCTION

- Voltage
raise or lower in tap changer device of power transformers.
- Frequency
regulation and load control.
- Power
system monitoring such as power factor control.
- Alarm
and indication control.
- Circuit
supervision.
- Audio/visual
annunciation.
B. CONTROL SYMBOLS AND ALPHABETS
In order to make for easy
identification, symbols and alphabets are used for various devices in control
circuits. This method helps to simplify
the control drawings. Control symbols
and alphabets generally used are as shown in Table 1. A clear knowledge of these facilitates the
understanding of the control drawings.
CONTROL CIRCUIT SUPPLIES
To effect operation of control
circuits, external auxiliary power supplies are used. Two major sources of supplies are most common
namely:
·
D.C.
supply
·
A.C.
supply
D. C. SUPPLY
The major source of D. C. supply is
from a storage battery. The storage
battery types commonly used are:
(a)
Lead
Acid Accumulator type
(b)
Nickel
Cadmium type.
Auxiliary D.C. supply has standard
voltage ratings of 24V, 30V, 36V, 48V, 50V, 60V, 72V, 110V, 220V and 250V. Generally 110V is used for Trip/Close
control. In some cases a combination of
50V and 110V D.C. are used. In this case
the relay coil energizes an auxiliary interposing relay whose contacts make to
energize an 110V D.C. breaker trip/close coil which in turn opens/closes the
contacts of a breaker.
Standard ampere-hour ratings of
auxiliary D.C. supply are 45, 60, 100, 250, 500 and 1000AH.
The voltage rating and the
Ampere-Hour rating are decided by:
(i)
The
size and capacity of the generating station and or substations.
(ii)
The
busbar switching arrangement, which decides the number of circuit breakers and
isolators.
(iii)
The
location of the control equipment in regard to the location of the controlled
apparatus i.e. the distance from the control room to the controlled apparatus.
In most 11KV, 33KV and 132KV
substations 110V DC batteries are
installed. In 330KV substations, both
50V DC and 110V DC batteries are used for control circuits.
The ampere-hour rating range between
100 and 250 AH.
A D. C. distribution panel is
generally associated with a D. C storage battery. The size of the panel depends upon the number
of individual circuits it serves. A
Non-fused breaker usually protects each sub-circuit of the distribution panel,
which trips as soon as a fault exists along the circuit being protected.
To protect the D. C. circuits from
ground fault, a ground fault relay is installed which usually flags whenever
there is a ground fault within any of the poles of the D.C circuits. For example, if there is a fault within the
positive pole of the
D. C. circuits, the D.C. ground
positive target of the ground fault relay will operate. The relay will not reset except the source of
the fault is cleared. In some cases, the
fault signal is wired to a visual alarm, which will indicate the actual pole
that is faulty. In some installations, a
switch is used to monitor the amount of voltage leaking to ground. Under normal conditions P-E and N-E voltages
are equal. But a pole loses the voltages
to ground if faulty.
A.C. SUPPLY
The A.C. supply for the control
circuits is obtained from a station auxiliary transformer. This, in the case of generating units, may be
directly connected to the generator terminals as unit auxiliary transformers.
A standby A.C generator is also used
as an alternate source of A.C. supply for control circuits. In stations where A.C. supply is to be
reliable, there could be two sources from which auxiliary supply is obtained
with an automatic change – over switch.
In this case, if supply from one source fails then, supply from the
other source is readily available. The
alternative source could be another auxiliary transformer from a separate
source, D.C. motor, A.C. generator set, or battery inverter circuit.
In control circuits, A.C. supply
could serve the following purposes:
(a) Control panel illumination
(b) Control panel heater
(c) Breaker spring operating motor.
(d) Breaker control panel heater and
illumination.
(e) Control panel indication lamps
(f)
Audio/visual
annunciation
(g) OLTC gear motor operation in power
transformers
(h) Position indication for tap – changer
progress.
TRIP CIRCUIT
The control circuit for the opening
of switchgear during normal operation or on fault is usually known as Trip
Circuit.
To ensure that this circuit does not
fail whenever a signal is sent to operate the breaker/disconnect switch, it is
being monitored continuously by a relay known as Trip Circuit Supervision
relay. The relay is wired in such a way
that the relay coil is energized as long as the trip circuit is healthy. If for any reason there is a fault within the
trip circuit causing a loss of D.C. supply, this relay de-energises causing the
mechanical target to flag, which will indicate, “Trip circuit faulty”. This relay is usually a self-reset relay,
which resets itself as soon as the D.C. supply is restored. D.C. supply can also be lost if the battery
charger is faulty or the D.C. fuse gets ruptured as a result of a short-circuit
fault within the D.C. circuit.
No comments:
Post a Comment