The following conditions must be strictly observed in
order that 3-phase transformers may operate in parallel.
(a) The secondaries must have the same
phase sequence or the same phase rotation.
(b) All corresponding secondary line
voltages must be in phase.
(c) The same inherent phase angle
difference between primary and secondary terminals.
(d) Same polarity.
(e) The secondaries must give the same
magnitude of line voltages.
In addition, it is desirable that:
(f)
The
impedances of each transformer, referred to its own rating should be the same,
i.e. each transformer should have the same percentage or per unit resistance
and reactance.
If
conditions (a) to (e) are not complied with, the secondaries will simply
short-circuit one another and no output will be possible.
If condition (f) is not complied
with, the transformers will not share the total load in proportion to their
ratings and one transformer will become over-loaded before the total output
reaches the sum of the individual ratings. It is difficult to ensure that
transformers in parallel have identical per unit impedance and this affects the
load sharing.
Three
Winding Power Transformers
An example of an EHV substation having three different
voltages is a 330KV substation with voltages at 330KV, 132KV and 11KV.
A comparison is now made as whether to have two winding
transformers of 330/132KV and 132/11KV or three winding transformers of
330/132/11KV in an EHV substation with three voltages. The 11KV load in such a substation is to meet
the local loads around the substation and also for the requirements of the
station auxiliary supplies. This load
may be around 10 to 15MVA.
Comparing scheme (B) with scheme (A) we have the following merits and demerits
Merits
(a) The number of transformers, circuit
breakers, CT’s, isolators and control panels is reduced to a minimum. There is therefore a considerable saving in
the cost of equipment required.
(b) There is considerable saving in the
cost of civil engineering and structural works because of the fewer equipment.
(c) The layout is simple and occupies
less space because of the fewer equipment
and
operation is also simple.
(d) There is saving in energy because of
the reduced transformation losses.
(e) Besides, it is inevitable to provide
a third winding in a star-star connected power transformer. This third winding in such transformers is
also called a `Stabilizing Winding' or ‘Tertiary Winding’. This winding is connected in a closed delta
to provide a circulating path for the third harmonic voltages and zero sequence
currents or ground fault currents.
It is pertinent to note
here that a star-star connection is almost always resorted to in the case of
EHV transformers of 132KV and above such as in 330/132KV transformers. The reason being that the cost of such a
transformer is cheaper because the windings need be insulated for only 1/Ö3 times of the line voltage instead
of for the full line voltage of Ö3 times the star voltage with a delta
winding. Such a closed delta winding can be made use of for the third voltage,
without the necessity of having a separate transformer.
Demerits
(a) The main disadvantage is the
increased fault level at 11KV because the voltage is directly transformed from
330 to 11KV. Hence 11KV switchgear of
adequately higher rupturing capacity will have to be installed.
The cost of such switchgear may be
much more than that of such switchgear installed in the secondary of a 132/11KV
transformer.
(b) Since the third winding is a closed
delta, an artificial neutral has to be necessarily
created by the use of earthing
transformers. This is a disadvantage as
it adds to the initial cost.
No comments:
Post a Comment